Boiler Enable Contact
The Boiler Enable terminals (7 and 8) are an isolated output in the
control. There is no power available on these terminals from the
control. These terminals are to be used as a switch to either make
or break the boiler limit circuit. When the control requires the boiler
to fire, it closes the contact between terminals 7 and 8.
Sensor and Unpowered Input Connections
Do not apply power to these terminals, as this will damage the control.
Boiler Return Sensor
Connect the two wires from the Boiler Return Sensor to the Com
and Boil Ret terminals (12 and 13). The boiler return sensor is used
by the control to measure the boiler return temperature.
Mix Sensor (Outdoor Reset and Setpoint Modes)
Connect the two wires from the Mix Sensor 071 to the Com and Mix
terminals (12 and 14). The mix sensor is used by the control to mea-
sure the mixed supply water temperature in the primary loop. Typi-
cally the sensor is attached to the pipe downstream of the system
pump.
Outdoor Sensor (Outdoor Reset Mode)
Connect the two wires from the Outdoor Sensor 070 to the Com and
Out terminals (15 and 16). The outdoor sensor is used by the control
to measure the outdoor air temperature.
7
Boiler
Enable
8
12
Com
13
Boil
Re
t
Boiler
Sensor
12
Com
13
Boil
Re
t
14
Mi
x
Mix Supply
Sensor
System
Pump
15
Com
16
Out
STEP SIX
TESTING THE WIRING
Each terminal block must be unplugged from its header on the control before power is applied for testing. To remove the terminal
block, pull straight down from the control.
The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly
trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 – 300 V (ac) and at least 0 – 2,000,000 Ohms, is essential to
properly test the wiring and sensors.